Contact us For registered customers Lietuvių По-русски
BASEC DNVGL

CYKY-L 5×2,5

Choose specification
Number of cores:
Choose cross-sectional area, mm²:

CYKY-L 5×2,5

The cable is designed for fixed electrical installations, laying the cable in wiring ducts or for electrical power distribution in electricity supply networks. The cables can be laid under the ground.

Soft and solid conductor is made from annealed copper wire. Copper core is PVC insulated.

Insulated cores are stranded together, coated with inner filler and PVC sheath. Cable is soft and easy to use

 

Additional information

The cable conformed with the EU Directive 2011/65/EU on the Restriction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment.

The cable conformed with the Low Voltage EU Directive 2014/35/EU.

The cable conformed with Regulation (EU) No 305/2011 of the European Parliament and of the Council.

Reaction to Fire Class Eca.  DoP (Declaration of Performance LK-DoP 02/002/EN)

Note: English CYKY-L datasheet

Note: Danish CYKY-L  Produktdatablad  Nominal voltage 450/750 V 

Technical date
Conductor resistance at +20°C In accordance with LST EN 60228+AC
Conductor working temeprature, max. +70°C (under normal conditions) +160°C (in the event of short circuit)
Thermal shock 1 h at +150°C
Rated voltage U/U0 450/750 V
High voltage test, kV 2 kV
Minimum bending radius During installation <= 10 D; Bending one time <= 8 D
Operating temperatures Mounting -5°C - +40°C Operating -30°C - +70°C
Flame propagation Flame test in accordance with LST EN 60332-1-2
Construction
Conductors Solid, annealed copper, class 1 in accordance with LST EN 60228+AC
Insuliation PVC insulation compound type TI1 in accordance with LST EN 50363-3
Core colours In accordance with LST HD 308
Sheath PVC sheathing compound type TM 1 in accordance with LST EN 50363-4-1
Sheath colour White, black or upon customer request
Grounding core Green/yellow in accordance with LST EN 50396
Filler EPDM
Number of cores 5
Cross-sectional area ofcores, mm² 2.5
Overall diameter of cables, mm 10.31
Cable approx. weight, kg/km 221
Laying In outside

See also


IS 201-4 flat

The cable is designed for electricity supply, lightning, and electrical installations. Soft conductor is made…


BS 6004 (flat)

The cable is designed for electricity supply, lightning, and electrical installations. Soft conductor is made…

© 1958 - 2021 AB „Lietkabelis“. All rights reserved. Created by A-GAIN